Details:

Code name Stockholm 3L
Mechanical Specifications    Metric   Imperial
Nominal Aluminum Cross-sectional Area* 453.7 mm2 895.4 kcmil
Nominal Diameter of Composite Core (CTC Part Number 200-006) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in2
Overall Diameter of Conductor 26.40 mm 1.039 in.
Nominal Cross-sectional Area of the Conductor 514.0 mm2 0.797 in2
Ultimate Tensile Strength of Conductor1,2 155.7 kN 35.0 kips
Rated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips
Core Nominal Mass per unit length 98 kg/km 66 lb/kft
Conductor Nominal Mass per unit length 1367.8 kg/km 919.3 lb/kft
Aluminum Nominal Mass per unit length** 1269.8 kg/km 853.4 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 356
Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 / 8.06E-07 /
Coefficient of Linear Expansion Below Thermal Kneepoint 1.85E-05 / 1.03E-05 /
Final Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 64.8 GPa 9.4 Msi
Electrical Specifications    Metric   Imperial
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0617 ohm/km 0.0993 ohm/mile
Temperature Coefficient of Resistance 0.00403   0.00403  
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0637 ohm/km 0.1031 ohm/mile
AC Nominal Resistance at 75ºC 0.0760 ohm/km 0.1228 ohm/mile
AC Nominal Resistance at 180ºC 0.1019 ohm/km 0.1642 ohm/mile
AC Current Rating at Given Temperature3   1039 @ 100C & 50 Hz
  1560 @ 180C & 50 Hz
GMR (estimated) 0.01 m 0.0000 ft
Inductive Reactance 0.644 ohm/km 1.244 ohm/mile
Capacitive Reactance 0.180 Mohm-km 0.093 Mohm-mile











































  • ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 467 sq. mm (921.7 kcmil).
  • ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient  temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation.
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
  • The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

[Next:Stockholm 2L]→

Related Products :

Conductor ACCC Brussels

Brussels
Conductor ACCC Brussels

Conductor ACCC Paris

Paris
Conductor ACCC Paris

Conductor ACCC  Lisbon

Lisbon
Conductor ACCC Lisbon

Conductor ACCC Budapest

Budapest
Conductor ACCC Budapest

Conductor ACCC Prague

Prague
Conductor ACCC Prague

Conductor ACCC  London

London
Conductor ACCC London

Conductor ACCC Casablanca

Casablanca
Conductor ACCC Casablanca

Conductor ACCC HELSINKI

HELSINKI
Conductor ACCC HELSINKI
Home   |    About Us   |    News   |    Products   |    Service   |    FAQ   |    Feedback   |    Contact Us   |    SiteMap
Copyright (c) 2014 Jiangsu Longyuan Electrical Equipment Co.,Ltd All Rights Reserved