Jiangsu Longyuan Electrical Equipment Co.,Ltd

Jiangsu Longyuan Electrical Equipment Co.,Ltd
Products

Conductor ACCC Oslo

Conductor ACCC Oslo

Product name:Conductor ACCC Oslo

Item:Oslo

Details:

code name Oslo
Mechanical Specifications    Metric   Imperial
Nominal Aluminum Cross-sectional Area* 313.8 mm2 619.3 kcmil
Nominal Diameter of Composite Core (CTC Part Number 200-006) 8.76 mm 0.345 in.
Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in2
Overall Diameter of Conductor 22.40 mm 0.882 in.
Nominal Cross-sectional Area of the Conductor 374.1 mm2 0.580 in2
Ultimate Tensile Strength of Conductor1,2 147.8 kN 33.2 kips
Rated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips
Core Nominal Mass per unit length 98 kg/km 66 lb/kft
Conductor Nominal Mass per unit length 980.2 kg/km 658.8 lb/kft
Aluminum Nominal Mass per unit length** 882.2 kg/km 592.9 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 356
Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 / 8.06E-07 /
Coefficient of Linear Expansion Below Thermal Kneepoint 1.70E-05 / 9.47E-06 /
Final Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 67.4 GPa 9.8 Msi
Electrical Specifications    Metric   Imperial
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0893 ohm/km 0.1437 ohm/mile
Temperature Coefficient of Resistance 0.00403   0.00403  
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0911 ohm/km 0.1476 ohm/mile
AC Nominal Resistance at 75ºC 0.1091 ohm/km 0.1764 ohm/mile
AC Nominal Resistance at 180ºC 0.1469 ohm/km 0.2369 ohm/mile
AC Current Rating at Given Temperature3   828 @ 100C & 50 Hz
  1234 @ 180C & 50 Hz
GMR (estimated) 0.01 m 0.0000 ft
Inductive Reactance 0.654 ohm/km 1.262 ohm/mile
Capacitive Reactance 0.189 Mohm-km 0.098 Mohm-mile











































  • ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 323 sq. mm (637.5 kcmil).
  • ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient  temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation.
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
  • The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

[Next:Munich]→

Related Products :

Conductor ACCC Mumbai

Mumbai
Conductor ACCC Mumbai

Conductor ACCC Glasgow

Glasgow
Conductor ACCC Glasgow

Conductor ACCC Berlin (HS Madrid)

Berlin (HS Madrid)
Conductor ACCC Berlin (HS Madrid)

Conductor ACCC Munich

Munich
Conductor ACCC Munich

Conductor ACCC Hamburg

Hamburg
Conductor ACCC Hamburg

Conductor ACCC Bordeaux

Bordeaux
Conductor ACCC Bordeaux

Conductor ACCC Kolkata

Kolkata
Conductor ACCC Kolkata

Conductor ACCC Brussels

Brussels
Conductor ACCC Brussels
Home   |    About Us   |    News   |    Products   |    Service   |    FAQ   |    Feedback   |    Contact Us   |    SiteMap
Copyright (c) 2013 Jiangsu Longyuan Electrical Equipment Co.,Ltd All Rights Reserved