Jiangsu Longyuan Electrical Equipment Co.,Ltd

Jiangsu Longyuan Electrical Equipment Co.,Ltd
Products

Conductor ACCC London

Conductor ACCC  London

Product name:Conductor ACCC London

Item:London

Details:

Code name London
Mechanical Specifications    Metric   Imperial
Nominal Aluminum Cross-sectional Area* 759.0 mm2 1497.9 kcmil
Nominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.
Nominal Cross-sectional Area of Core 75.1 mm2 0.116 in2
Overall Diameter of Conductor 33.40 mm 1.315 in.
Nominal Cross-sectional Area of the Conductor 834.1 mm2 1.293 in2
Ultimate Tensile Strength of Conductor1,2 204.8 kN 46.0 kips
Rated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kips
Core Nominal Mass per unit length 143 kg/km 96 lb/kft
Conductor Nominal Mass per unit length 2248.1 kg/km 1510.9 lb/kft
Aluminum Nominal Mass per unit length** 2105.1 kg/km 1414.8 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 356
Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 / 8.94E-07 /
Coefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 / 1.09E-05 /
Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 62.9 GPa 9.1 Msi
Electrical Specifications    Metric   Imperial
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0370 ohm/km 0.0595 ohm/mile
Temperature Coefficient of Resistance 0.00403   0.00403  
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0391 ohm/km 0.0639 ohm/mile
AC Nominal Resistance at 75ºC 0.0464 ohm/km 0.0754 ohm/mile
AC Nominal Resistance at 180ºC 0.0616 ohm/km 0.0996 ohm/mile
AC Current Rating at Given Temperature3   1424 @ 100C & 50 Hz
  2164 @ 180C & 50 Hz
GMR (estimated) 0.01 m 0.0000 ft
Inductive Reactance 0.630 ohm/km 1.217 ohm/mile
Capacitive Reactance 0.166 Mohm-km 0.086 Mohm-mile











































  • ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 781.3 sq. mm (1541.9 kcmil).
  • ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient  temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation.
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
  • The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

[Next:Lisbon]→

Related Products :

Conductor ACCC Glasgow

Glasgow
Conductor ACCC Glasgow

Conductor ACCC Berlin (HS Madrid)

Berlin (HS Madrid)
Conductor ACCC Berlin (HS Madrid)

Conductor ACCC Hamburg

Hamburg
Conductor ACCC Hamburg

Conductor ACCC Bordeaux

Bordeaux
Conductor ACCC Bordeaux

Conductor ACCC Kolkata

Kolkata
Conductor ACCC Kolkata

Conductor ACCC Brussels

Brussels
Conductor ACCC Brussels

Conductor ACCC  Lisbon

Lisbon
Conductor ACCC Lisbon

Conductor ACCC Budapest

Budapest
Conductor ACCC Budapest
Home   |    About Us   |    News   |    Products   |    Service   |    FAQ   |    Feedback   |    Contact Us   |    SiteMap
Copyright (c) 2013 Jiangsu Longyuan Electrical Equipment Co.,Ltd All Rights Reserved