Product name:Conductor ACCC Brussels

Item:Brussels

Details:

Code name Brussels
Mechanical Specifications    Metric   Imperial
Nominal Aluminum Cross-sectional Area* 421.4 mm2 831.6 kcmil
Nominal Diameter of Composite Core (CTC Part Number 200-006) 8.13 mm 0.320 in.
Nominal Cross-sectional Area of Core 51.9 mm2 0.080 in2
Overall Diameter of Conductor 25.15 mm 0.990 in.
Nominal Cross-sectional Area of the Conductor 473.3 mm2 0.734 in2
Ultimate Tensile Strength of Conductor1,2 135.7 kN 30.5 kips
Rated Strength of Core - 313 ksi (2158 MPa) 112.0 kN 25.2 kips
Core Nominal Mass per unit length 98 kg/km 66 lb/kft
Conductor Nominal Mass per unit length 1264.8 kg/km 850.1 lb/kft
Aluminum Nominal Mass per unit length** 1166.8 kg/km 784.2 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 356
Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 / 8.94E-07 /
Coefficient of Linear Expansion Below Thermal Kneepoint 1.89E-05 / 1.05E-05 /
Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 64.0 GPa 9.3 Msi
Electrical Specifications    Metric   Imperial
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0666 ohm/km 0.1072 ohm/mile
Temperature Coefficient of Resistance 0.00403   0.00403  
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0687 ohm/km 0.1110 ohm/mile
AC Nominal Resistance at 75ºC 0.0820 ohm/km 0.1323 ohm/mile
AC Nominal Resistance at 180ºC 0.1099 ohm/km 0.1771 ohm/mile
AC Current Rating at Given Temperature3   987 @ 100C & 50 Hz
  1479 @ 180C & 50 Hz
GMR (estimated) 0.01 m 0.0000 ft
Inductive Reactance 0.647 ohm/km 1.250 ohm/mile
Capacitive Reactance 0.183 Mohm-km 0.095 Mohm-mile













































  • ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 433.8 sq. mm (856.1 kcmil).
  • ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient  temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation.
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
  • The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

[Next:Bordeaux]→

Related Products :

Conductor ACCC Bordeaux

Bordeaux
Conductor ACCC Bordeaux

Conductor ACCC Athens

Athens
Conductor ACCC Athens

Conductor ACCC Amsterdam

Amsterdam
Conductor ACCC Amsterdam

Conductor ACCC Berlin (HS Madrid)

Berlin (HS Madrid)
Conductor ACCC Berlin (HS Madrid)

Conductor ACCC Antwerp

Antwerp
Conductor ACCC Antwerp

Conductor ACCC HELSINKI

HELSINKI
Conductor ACCC HELSINKI
Home   |    About Us   |    News   |    Products   |    Service   |    FAQ   |    Feedback   |    Contact Us   |    SiteMap
Copyright (c) 2013 Jiangsu Longyuan Electrical Equipment Co.,Ltd All Rights Reserved