Jiangsu Longyuan Electrical Equipment Co.,Ltd

Jiangsu Longyuan Electrical Equipment Co.,Ltd
Products

Conductor ACCC Bordeaux

Conductor ACCC Bordeaux

Product name:Conductor ACCC Bordeaux

Item:Bordeaux

Details:

Code name Bordeaux
Mechanical Specifications    Metric   Imperial
Nominal Aluminum Cross-sectional Area* 880.9 mm2 1738.4 kcmil
Nominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.
Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in2
Overall Diameter of Conductor 35.76 mm 1.408 in.
Nominal Cross-sectional Area of the Conductor 968.2 mm2 1.501 in2
Ultimate Tensile Strength of Conductor1,2 237.9 kN 53.5 kips
Rated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kips
Core Nominal Mass per unit length 164 kg/km 110 lb/kft
Conductor Nominal Mass per unit length 2766.2 kg/km 1859.1 lb/kft
Aluminum Nominal Mass per unit length** 2602.2 kg/km 1748.9 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 /oC 1.09E-05 /oF
Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 62.9 GPa 9.1 Msi
Electrical Specifications    Metric   Imperial
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0318 ohm/km 0.0512 ohm/mile
Temperature Coefficient of Resistance 0.00403   0.00403  
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0340 ohm/km 0.0559 ohm/mile
AC Nominal Resistance at 75ºC 0.0402 ohm/km 0.0656 ohm/mile
AC Nominal Resistance at 180ºC 0.0531 ohm/km 0.0861 ohm/mile
AC Current Rating at Given Temperature3   1560 @ 100C & 50 Hz
  2381 @ 180C & 50 Hz
GMR (estimated) 0.01 m 0.0000 ft
Inductive Reactance 0.626 ohm/km 1.208 ohm/mile
Capacitive Reactance 0.162 Mohm-km 0.084 Mohm-mile










































  • ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 906.8 sq. mm (1789.6 kcmil).
  • ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient  temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation.
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).
  • The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

[Next:Berlin (HS Madrid)]→

Related Products :

Conductor ACCC Berlin (HS Madrid)

Berlin (HS Madrid)
Conductor ACCC Berlin (HS Madrid)

Conductor ACCC Athens

Athens
Conductor ACCC Athens

Conductor ACCC Antwerp

Antwerp
Conductor ACCC Antwerp

Conductor ACCC Amsterdam

Amsterdam
Conductor ACCC Amsterdam

Conductor ACCC HELSINKI

HELSINKI
Conductor ACCC HELSINKI
Home   |    About Us   |    News   |    Products   |    Service   |    FAQ   |    Feedback   |    Contact Us   |    SiteMap
Copyright (c) 2013 Jiangsu Longyuan Electrical Equipment Co.,Ltd All Rights Reserved