Jiangsu Longyuan Electrical Equipment Co.,Ltd

Jiangsu Longyuan Electrical Equipment Co.,Ltd
Products

Conductor ACCC Amsterdam

Conductor ACCC Amsterdam

Product name:Conductor ACCC Amsterdam

Item:Amsterdam

Details:

Code name Amsterdam
Mechanical Specifications    Metric   Imperial
Nominal Aluminum Cross-sectional Area* 367.4 mm2 725.1 kcmil
Nominal Diameter of Composite Core (CTC Part Number 200-005) 7.75 mm 0.305 in.
Nominal Cross-sectional Area of Core 47.1 mm2 0.073 in2
Overall Diameter of Conductor 23.55 mm 0.927 in.
Nominal Cross-sectional Area of the Conductor 414.5 mm2 0.642 in2
Ultimate Tensile Strength of Conductor1,2 122.4 kN 27.5 kips
Rated Strength of Core - 313 ksi (2158 MPa) 101.7 kN 22.9 kips
Core Nominal Mass per unit length 86 kg/km 58 lb/kft
Conductor Nominal Mass per unit length 1101.6 kg/km 740.4 lb/kft
Aluminum Nominal Mass per unit length** 1015.6 kg/km 682.6 lb/kft
Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF
Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /oF
Coefficient of Linear Expansion Below Thermal Kneepoint 1.88E-05 /oC 1.04E-05 /oF
Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi
Final Modulus of Elasticity Below Thermal Kneepoint 64.2 GPa 9.3 Msi
Electrical Specifications    Metric   Imperial
Nominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0762 ohm/km 0.1226 ohm/mile
Temperature Coefficient of Resistance 0.00403   0.00403  
Frequency 50 Hz 60 Hz
AC Nominal Resistance at 25ºC 0.0784 ohm/km 0.1265 ohm/mile
AC Nominal Resistance at 75ºC 0.0936 ohm/km 0.1510 ohm/mile
AC Nominal Resistance at 180ºC 0.1256 ohm/km 0.2024 ohm/mile
AC Current Rating at Given Temperature3   907 @ 100C & 50 Hz
  1355 @ 180C & 50 Hz
GMR (estimated) 0.01 m 0.0000 ft
Inductive Reactance 0.652 ohm/km 1.258 ohm/mile
Capacitive Reactance 0.186 Mohm-km 0.097 Mohm-mile
















































  • ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 378.2 sq. mm.
  • ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature.
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient     temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation.
4) Maximum continuous operating temperature of ACCC® is 180°C and a maximum emergency               temperature of 200°C (10,000 hours over the life of the conductor).
  • The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.